EPA Section 608 Technician Certification practice test
Built for the EPA Section 608 Technician Certification test, for anyone who services or disposes of stationary refrigeration and air conditioning equipment: Core, Type I small appliances, Type II high-pressure systems and Type III low-pressure chillers, so you can practice for one type or go for Universal. Every question is original and written against the current federal refrigerant rules (40 CFR Part 82 Subpart F, and the HFC rules in Part 84 that took effect in 2026), with an explanation of why the right answer is right.
Try the free sample Buy the full set, $12 once
The free sample is 10 questions, graded, with no sign-up. Or get All-access for $9/month: every test on the site. An account keeps your progress on every device.
What the full set includes
- 200 original four-option questions, with an explanation for every answer
- 8 practice exams: two each for Core, Type I, Type II and Type III, 25 questions apiece like the real sections
- Each exam graded against 70 percent, the passing score for each section of the real closed-book test; take all four for a Universal run
- Study mode (instant feedback) and exam mode (timer, graded at the end)
- Drill by topic or only your weak spots; weak spots tracked across every attempt
Topics covered
- Core: environmental impact
- Core: industry outlook and refrigerants
- Core: laws and regulations
- Core: service practice and safety
- Type I: leak detection
- Type I: recovery techniques
- Type I: safety
- Type I: shipping and disposal
- Type II: leak detection and repair
- Type II: recovery techniques
- Type II: safety
- Type II: shipping and disposal
- Type III: leak detection
- Type III: recovery techniques
- Type III: safety
- Type III: shipping and disposal
Sample questions
Question 1
A tech lets the charge of R-410A blow off into the air while replacing a coil. What does the venting ban say about that?
- It is allowed, because R-410A has no chlorine and does not harm the ozone layer
- It is allowed as long as the unit holds less than 50 pounds of refrigerant
- It is a violation, since the ban covers non-exempt substitutes too
- It is allowed when the work is done outdoors where the vapor spreads out
Show the answer
C. It is a violation, since the ban covers non-exempt substitutes too. The venting prohibition in 40 CFR 82.154 covers class I and class II refrigerants and also substitutes such as HFCs that are not on the exempt list. Having no ozone depletion potential does not make a knowing release legal.
Question 2
Which of these is a small appliance under the EPA definition?
- A split system charged at the job site with 4 pounds of refrigerant
- A factory-charged rooftop package unit holding 8 pounds of refrigerant
- A factory-sealed window air conditioner holding 3 pounds
- A walk-in cooler with its line set brazed on site, 5 pounds
Show the answer
C. A factory-sealed window air conditioner holding 3 pounds. A small appliance is fully manufactured, charged and hermetically sealed in a factory with 5 pounds or less of refrigerant. Anything charged or assembled in the field, or over 5 pounds, is not a small appliance.
Question 3
A technician recovers refrigerant from a high-pressure appliance with a 150 pound charge, using recovery equipment made after 1993. What vacuum must be reached before opening it?
- 0 inches of mercury vacuum
- 4 inches of mercury vacuum
- 10 inches of mercury vacuum
- 15 inches of mercury vacuum
Show the answer
A. 0 inches of mercury vacuum. Table 1 in 40 CFR 82.156 sets 0 inches of mercury for a high-pressure appliance with a full charge under 200 pounds. The 10 and 15 inch levels apply to larger or medium-pressure appliances.
Not affiliated with or endorsed by the U.S. Environmental Protection Agency or any EPA-approved certifying organization. The questions here are original practice material and are not the official test. Only an EPA-approved certifying program can certify a technician.